Northwest Tank offers Underground Storage Tank (UST) Compliance
Testing which includes all required release detection testing
procedures. A failure
to comply
with local,
state and federal requirements related to detection testing may result
in written violations and monetary
fines.
Because testing frequency and fuel requirements are often site
specific, Northwest Tank evaluates each site specifically to determine
minimum test requirements and provides a cost estimate for any
necessary
testing free of charge.
To ensure ongoing compliance, Northwest Tank clients are enrolled
in a “UST
Compliance Program” that is specific to the unique needs of
the station. The site is notified prior to the next required testing
period to ensure that the next testing cycle is conducted on-time.
Clients who participate in the UST Compliance Program and are under
contract
with Northwest Tank are guaranteed timely service. This means that
if the site is not tested on or before the next scheduled due date,
the
testing service for that cycle is provided at no cost. Contact
Northwest Tank for more information.
Tank Tightness Testing
Tank Tightness Testing is required in the event of a failed or non-conclusive
Statistical Inventory Reconciliation (SIR) report, as mandated by
local, state or federal inspectors, or as required by the owner’s
insurance company.
Requirements for Tank Tightness Testing:
- Maximum of 20,000 gallon capacity for each tank.
- Minimum of 24 inches
of product in each tank.
- Minimum of 12 hours waiting period after
fuel delivery.
- Maximum of 10,000 gallons Ullage (vapor space).
- Minimum 1 hour
test time.
- Typical down-time for test: 2-5 hours.
For more information about third-party certification click
here.
Line Tightness Testing
Line Tightness Testing is required annually for all single-wall,
pressurized, underground product lines that are not equipped with
SIR or an electronic line leak detector capable of conducting a monthly
.2GPH test. Suction systems with a check valve located at the tank
require line tightness testing once every three years.
Requirements for Line Tightness Testing:
- Minimum of 30 minute period between dispensing and testing.
- Minimum
30 minute test.
- Test conducted at 150% normal operating pressure.
- Typical down-time
for test: 1 hour.
For more information about third-party certification click
here.
Leak Detector Testing
Leak Detector Testing is required annually for all underground pressurized
lines regardless of line configuration. A 3GPH leak must be simulated
by a licensed technician once a year to ensure the line is protected
from a catastrophic failure.
Requirements for Leak Detector Testing:
- Access to circuit breaker and turbine relay boxes.
- Simulate 3GPH leak
at a metering pressure of 10 PSI.
- Typical down-time for test: 30-45
minutes.
Cathodic Protection System
Steel tanks equipped with a Cathodic Protection (CP) system require
testing once every three years at a minimum. In addition, sites equipped
with an impressed current system have a rectifier which requires
inspection once every 60 days. Owner/operators may conduct the 60-day
inspections, however, a certified CP tester is required for the three
year test.
Requirements for Cathodic Protection System Testing:
- Access to the rectifier (if applicable).
- Access to the protected
structures (tanks, lines, etc.).
- Site or products will
only require down-time in the event the protected structures
are located in a high-traffic area near the fuel dispensing
area.
- Typical test time: 30-45 minutes per tank.
return
to top
Tank Monitor Certifications
Monitoring systems are required to be tested in accordance with
manufacturer guidelines. Northwest Tank’s team of experienced
and highly trained technicians can thoroughly inspect the programming,
sensor placement, and sensor operation of such monitoring systems
in accordance with established manufacturer guidelines.
To learn more about third-party evaluations and to determine the
testing requirements for your monitoring system click
here.
Requirements:
- Access to monitoring system console.
- Access to all sensors or probes.
- Typical down-time for test: 1-2 hours
depending on the number of components in the system. Sites
not programmed for positive shut-down
with tanks away from high traffic dispensing area may not
have any down-time for this test.
return to top
Helium Pinpoint Testing
Helium Pinpoint Testing is strictly used as a troubleshooting tool
to locate a suspected leak. This is not an authorized form of release
detection. However, proper helium pinpoint testing will locate a
leak and potentially save the site owner time and money by determining
the exact leak location, thus allowing maintenance crews to dig in
the correct spot to conduct the needed repair.
Requirements for Helium Pinpoint Testing:
- Line or tank must be empty for test.
- Typical down-time varies depending
on ground cover, system size, etc.